You badge in, the door buzzes, you pull, and nothing happens. By the time you have tried twice more the buzz has stopped and you are badging again. It is one of the most common access control complaints in a commercial building, and it is almost never the reader or the card that is at fault.
First, work out what is holding the door
Everything downstream depends on this, and it takes about ten seconds to establish. Two completely different devices produce the same symptom, and they fail for opposite reasons.
An electric strike
The strike is the part fixed in the frame that the latch goes into. An electric strike replaces that fixed box with one that has a hinged keeper. When the system releases, the keeper is free to pivot, so the latch can swing out of it and the door opens while the latch itself stays extended. The lock on the door is untouched and still mechanical.
Look at the frame on the latch side. If there is a metal unit with a visible moving lip and a wire running into the frame, you have an electric strike.
A magnetic lock
A mag lock works nothing like that. An electromagnet mounts on the frame at the head of the door, an armature plate mounts on the door itself, and while the magnet is energised the two clamp together with considerable force. Release means cutting power to the magnet. There is no latch and no keeper involved.
Look at the top of the door. A rectangular block on the frame with a matching plate on the door is a mag lock.
Why an electric strike buzzes but will not let go
The buzz is the keeper vibrating at mains frequency, which tells you power is arriving. If it buzzes and the door still will not open, the mechanism is being physically prevented from releasing, and there is a short list of reasons.
Preload
This is the big one and the one most often missed. Preload is sideways pressure on the latch pushing it against the keeper. It comes from a door closer holding the door tight, from a door that has swelled or dropped, from stack pressure in a stairwell, or simply from someone leaning on the door while they badge. A standard electric strike cannot release against meaningful preload, because the latch is jammed into the keeper and the keeper cannot pivot past it.
The giveaway: push the door firmly closed, or pull it slightly towards you, then badge. If it suddenly works, you have found preload. Strikes rated to release under preload exist, and where the condition is structural rather than occasional, specifying one is the real fix.
Alignment
The latch has to sit in the keeper the way the designer intended. If the door has dropped on its hinges, or the frame has moved, the latch may be riding high, low or deep in the keeper and binding against the casing. Witness marks inside the strike usually show exactly where it is rubbing.
Not enough power at the device
A strike that buzzes weakly, works intermittently, or works for the first person in the morning and not the fifth may be undervolted. Long cable runs, undersized conductors and power supplies carrying more devices than they were sized for all drop voltage at the far end. Measuring at the device while it is energised, rather than at the panel, is what settles this.
Wrong failure mode for the application
Strikes come as fail-secure, which stay locked when power is lost, and fail-safe, which release. If a door has been fitted with the wrong one for its role, it may be doing exactly what it was built to do while being completely unsuitable for the opening. This matters most on doors in an escape route, where the behaviour on power loss and on fire alarm is not a preference, it is a requirement.
Why a mag lock will not release
The failure pattern here is different because there is no mechanism, only a magnet.
- Residual magnetism. Power is off but the magnet and armature stay tacked together for a moment. Good installations include features to counter this; cheap or aged ones may hold for a second or two, which is long enough for someone to decide the door is locked and walk away.
- Power genuinely not cut. The release relay has failed closed, a request-to-exit device is not registering, or the controller is not dropping the output. The door is simply still locked.
- Mechanical binding. The magnet released but the door is sticking in its frame for unrelated reasons, usually a dropped door or a closer set too hard. Easy to misread as a lock fault.
- Armature plate movement. The plate is meant to be mounted with a small amount of float so it can seat flat against the magnet. Overtightened, or loose and misaligned, it misbehaves at both ends of the cycle.
Mag locks also carry obligations that strikes do not. Because the only thing holding the door is power, the arrangements for releasing it on fire alarm, on loss of power and on a push to exit have to be right. If you are not certain how a particular mag-locked door in your building behaves when the alarm sounds, that is worth establishing deliberately rather than discovering during an evacuation. A contractor who handles electric strike and mag lock work as part of their normal workload should be able to demonstrate it to you on site.
A diagnostic order that saves time
- Identify the device. Strike in the frame, or magnet at the head. Do not skip this.
- Test for preload. Relieve pressure on the door and try again. A door that then opens has told you the answer.
- Separate the lock from the door. With the lock released, does the door swing freely? If not, the complaint is a door problem wearing an access control costume.
- Check the signal is arriving. Buzz, click or no sound at all narrows it immediately: no sound on a strike usually means no power or no release command.
- Measure voltage at the device under load. Not at the supply.
- Check the mechanical lock behind it. A worn latch, a seized cylinder or a lock that no longer throws properly will defeat a perfectly good strike. This is the point at which commercial lock repair becomes the actual job.
One broader point. If a door is heavily used, needs to be accessible, and keeps generating complaints, the honest answer is sometimes that it is the wrong arrangement for the traffic it carries. A door people have to pull hard while holding a badge is a door that will keep failing in small ways. Fitting a powered operator changes the problem rather than patching it, and on an entrance that has to be usable by everyone it is often the correct specification from the start.
Frequently asked questions
Why does the door open fine in the morning and stick later in the day?
Temperature and traffic. Doors and frames move as the building warms, and a latch with a small margin in the keeper can start binding. On mag locks, a door that has been slammed repeatedly through the day may be sitting differently against the armature.
Is a buzzing strike broken?
No, the buzz is normal on AC-powered strikes and simply means it is energised. A strike buzzing while the door refuses to open is pointing at preload, alignment or voltage, not at itself.
Can I just fit a stronger mag lock?
Rarely the right answer. If a mag lock is being defeated, the issue is usually mounting, alignment or the armature plate rather than holding force, and more force on a badly mounted lock makes the door harder to use without making it more secure.
Our door releases but swings shut too fast to get through. What is that?
The door closer, not the access control. Closers have separate adjustments for sweep and latch speed, and a closer that has been wound up or has aged will shut a door faster than people can walk through it. It is adjustable.
Does losing power unlock our doors?
It depends entirely on how each door was specified, and the answer may differ door to door in the same building. Mag locks release when power is lost by design. Electric strikes may stay locked or release depending on which type is fitted. This is worth having documented for your building rather than guessed at.